ArmaProtect FC2: Firestop Collar for Walls & Floors

ArmaProtect FC2 is a robust firestop collar featuring a solid metal sleeve and multi-layered intumescent material, designed to maintain fire resistance for pipe penetrations in walls and floors. Essential for passive fire protection in Saudi Arabia and Bahrain. Available at Gitco-sa.com.

Description

ArmaProtect FC2 is a high-performance firestop collar engineered to provide crucial passive fire protection by maintaining the fire resistance performance of pipe penetrations in walls and floors. It features a solid metal sleeve – powder-coated sheet steel for diameters up to 200mm and galvanized sheet steel for diameters 225mm and above – equipped with several layers of advanced intumescent material. In the event of a fire, this intumescent inlay rapidly expands (18 to 38 times its original volume), sealing off the penetration and preventing the spread of fire and smoke. Gitco-sa.com, as the authorized Armacell distributor for Saudi Arabia and Bahrain, ensures that this vital safety product is available across the region, serving critical construction projects in key locations like Riyadh, Jeddah, Dammam, and Manama.

Designed for durability and reliability, ArmaProtect FC2 operates within a broad temperature range of -40°C to 70°C, with an optimal processing temperature of 5°C to 25°C. The collar’s housing is classified as Class A1 for Reaction to Fire, while the intumescent inlay is Class E (EN 13501-1). This firestop collar is certified for use in conditions exposed to weathering (Type X, EOTA TR 024), highlighting its robustness for various environments. It delivers impressive fire resistance, offering up to EI 120 for drywall, concrete, aerated concrete, masonry walls, and concrete floors (EN 13501-2). ArmaProtect FC2 ensures no dangerous substances are emitted, complying with health and safety standards. With no specified shelf life when stored correctly (cool, dry, protected from frost), ArmaProtect FC2 provides long-term, reliable passive fire protection for your building’s integrity.

Key Features of ArmaProtect FC2:

  • Solid Metal Sleeve: Provides robust structural integrity and support.
  • Multi-Layer Intumescent Material: Rapidly expands (18-38x) to seal penetrations during a fire.
  • High Fire Resistance: Up to EI 120 for various wall and floor types (EN 13501-2).
  • Wide Operating Temperature: Effective from -40°C to 70°C.
  • Weather-Exposed Use (Type X): Suitable for applications with exposure to weathering.
  • No Dangerous Substances: Safe for installation and long-term occupancy.
  • Powder-Coated/Galvanized Steel Housing: Ensures durability and corrosion resistance.

Product Variations of ArmaProtect FC2:

ArmaProtect FC2 is primarily differentiated by the pipe diameter it accommodates, with the housing material varying based on size (powder-coated sheet steel for smaller diameters, galvanized for larger). The product comes in pre-defined sizes to match common pipe diameters encountered in construction. While the core “FC2” technology remains consistent, the variations in diameter mean that clients can select the exact collar needed for their specific pipe penetration requirements. For detailed information on available diameters and precise fire rating data for different pipe materials and wall/floor constructions, please consult Gitco-sa.com.

Know more about”ArmaProtect FC2″:

  1. What is ArmaProtect FC2?
    ArmaProtect FC2 is a pre-formed firestop collar from Armacell, consisting of a solid metal sleeve (powder-coated or galvanized sheet steel housing) equipped with multiple layers of flexible intumescent material. It’s designed for sealing pipe penetrations in fire-rated walls and floors.
  2. What is the primary function of ArmaProtect FC2?
    Its primary function is to maintain the fire resistance performance of fire-rated walls and floors when penetrated by pipes, effectively preventing the spread of fire, smoke, and toxic gases from one compartment to another.
  3. How does ArmaProtect FC2 work in a fire?
    The intumescent material inside the collar expands significantly (18 to 38 times its original volume) when exposed to heat (above ). This expansion creates a high-pressure char that crushes combustible pipes (like PVC, PE, PP) or seals the annular gap around non-combustible pipes, blocking fire and smoke passage.
  4. What types of pipes can ArmaProtect FC2 be used with?
    ArmaProtect FC2 is primarily used for combustible pipes (e.g., PVC, PE, PP), and importantly, it can seal these pipes without insulation up to large diameters, specifically up to . It can also be used for other pipe types depending on the tested system.
  5. What kind of fire resistance ratings can ArmaProtect FC2 achieve?
    When properly installed in approved wall and floor constructions (drywall, concrete wall, aerated concrete wall, masonry wall, concrete floors), it can achieve high fire resistance ratings, typically up to EI 120 (120 minutes of integrity and insulation). Some systems might allow for higher ratings depending on the application.
  6. What material is the outer casing (sleeve) of ArmaProtect FC2 made from?
    The housing is made of powder-coated sheet steel (for diameters up to 200 mm) or galvanized sheet steel (for diameters ).
  7. What material is the intumescent inlay of ArmaProtect FC2 made from?
    The intumescent inlay is a flexible intumescent strip based on blowing graphite technology.
  8. What is the color of the ArmaProtect FC2 housing and inlay?
    The housing is typically grey, and the intumescent material inlay is anthracite (dark grey/black).
  9. How does ArmaProtect FC2 differ from ArmaProtect FC1?
    Both are pre-formed firestop collars. The key difference lies in the maximum pipe diameter they can seal:

    • ArmaProtect FC1: For combustible pipes without insulation up to .
    • ArmaProtect FC2: For combustible pipes without insulation up to , making it suitable for much larger pipes.
  10. What are the key benefits of using ArmaProtect FC2?
    Key benefits include:

    • Large diameter pipe sealing: Unique capability for pipes up to 400 mm.
    • Pre-formed product: Simplifies installation and ensures consistent application.
    • Clean installation: Less mess compared to other firestop methods.
    • Easy visual inspection: Allows for straightforward post-installation checks.
    • Reliable fire and smoke sealing.
  11. How is ArmaProtect FC2 installed?
    The collar is fitted around the pipe where it penetrates the fire-rated wall or floor. It is then mechanically fixed to the wall or floor structure using appropriate fasteners (e.g., screws). Detailed installation instructions specific to the pipe type and building element must be followed, often available in application videos and technical handbooks.
  12. Are there different sizes available for ArmaProtect FC2?
    Yes, it is available in a range of diameters, typically from 32 mm up to 400 mm, to fit various pipe sizes.
  13. Is ArmaProtect FC2 compliant with international fire safety standards?
    Yes, it is globally tested and approved with European Technical Assessments (ETA) and complies with fire resistance testing standards like EN 1366-3 (fire resistance tests for service installations – penetration seals) and EN 13501-2 (fire classification of construction products and building elements).
  14. What is the operating temperature range for ArmaProtect FC2?
    The operating temperature range is typically from to .
  15. Does ArmaProtect FC2 release dangerous substances?
    No, according to Armacell, there is no emission of dangerous substances, contributing to a healthier environment.
  16. Is ArmaProtect FC2 suitable for both rigid and flexible wall/floor constructions?
    Yes, it is designed for use in various rigid constructions such as drywall, concrete walls, aerated concrete walls, masonry walls, and concrete floors.
  17. Does ArmaProtect FC2 contribute to preventing smoke spread?
    Yes, its intumescent action creates a tight seal that effectively prevents the passage of smoke and toxic gases, which is crucial for safe evacuation during a fire.
  18. Is ArmaProtect FC2 intended for professional use only?
    Yes, firestop products like ArmaProtect FC2 are typically designated for professional use only to ensure correct installation and compliance with fire safety regulations.
  19. Where can one purchase ArmaProtect FC2 in Bahrain and Saudi Arabia?
    Gitco-sa.com, as an authorized distributor and partner of Armacell in Saudi Arabia and Bahrain, would be a primary supplier for ArmaProtect FC2. They would offer this product as part of Armacell’s comprehensive passive fire protection portfolio.
  20. Why choose a specialized supplier like Gitco-sa.com for ArmaProtect FC2 in Bahrain/Saudi Arabia?
    Choosing a specialist ensures access to genuine Armacell products with validated technical performance. Gitco-sa.com can provide critical technical expertise on product selection, precise installation methods, and compliance with local fire safety codes and regulations, which are essential for ensuring the safety and integrity of buildings in the region.

Reviews

There are no reviews yet.

Be the first to review “ArmaProtect FC2: Firestop Collar for Walls & Floors”